Description
The DRF-PR signal regulator receives DC process signal input and provides isolated output signals of 0-10 Vdc or 4-20 mA. There are three different power supply options available for you to choose from: 24 Vdc, 120 Vac, and 240 Vac.
DRF-PR is the ideal choice for industrial applications. All models can be installed on standard 35 mm DIN rails and provide up to 3500 Veff (model specific) electrical isolation between input, output, and power supply. The module response time is 70 ms or faster.
Specifications:
Accuracy: less than 0.2% of full scale
Linearity: less than 0.1% of full scale
Thermal drift: 150 ppm/° C (conventional) (maximum<200 ppm/° C) Response time (DC signal input model): less than 70mS (90% of the signal) at 20 Hz -3 dB Input impedance: 50 Ω in the range of 4-20 mA and 0-20 mA; 20 Ω when the range is 0-5 mA and 0-50 mA; 5 M Ω when the range is ≤ 1V; 1 M Ω at range=10V Over range protection: 3.5 Vdc at 4-20 mA and 0-20 mA ranges; 2.5 Vdc when the range is 0-5 mA and 0-50 mA; 15V when the range is 1V; 150V at range=10V Excitation output voltage of the sensor:+15 Vdc ± 10% (maximum current 22 mA) Code: DRF-PR-115VAC-0/10VDC-4/20 DRF-PR-115VAC-0/10VDC-0/10 Buyer Notice 1. About the product Due to market fluctuations, exchange rate changes, and other factors, product prices and product attributes are for reference only; The specific product requirements are subject to customer requirements, and the price is based on the communicated quotation. All product prices on this website are not considered transaction prices and are for reference only! 2. About Trademark Copyright All company names, trademarks, logos, product images, product descriptions, product brand names, and trademark copyrights related to this website belong to the corresponding brands; This website is only designed for the convenience of product identification. Please carefully read the buyer's instructions to avoid unnecessary disputes.
Reviews
There are no reviews yet.